HP TRANSFORMER OILS
Meets Specifications:
HP TRANSFORMER OIL exceeds IS: 335:1993 (Reaffirmed 2005) performance levels. It also meets IS:335-2018 TYPE II UNINHIBITED.
Detail Description:
HP TRANSFORMER OIL is designed for human safety and free from carcinogenic Poly chlorinated Bi-phenyls (PCB) and Poly aromatic hydrocarbon (PAH).
PROPOSED USAGE:
- Electric transformers
- Switch gears
- Circuit breakers which require insulating fluids
- Has very high oxidation stability
- Excellent ageing properties resulting in long product life
Physico-chemical Properties:
PROPERTIES | HP TRANSFORMER OILS |
---|---|
Appearance | Clear and transparent and free from suspended matter of sediments |
Density at 29.5 ºC, g/cc | 0.8279 |
Kinematic viscosity, cst At 27ºC At 40ºC |
16.46 11 |
Interfacial tension at 27ºC | 0.044 N/m |
Flash point pensky-marten (closed),ºC | 172 |
Pour point,ºC | -18 |
Neutralization value, mg KOH/g a) Total acidity b) Inorganic acidity/alkalinity |
Nil Nil |
Corrosive sulphur | Non corrosive |
Electric strength (breakdown voltage) –kV(rms) a) New unfiltered oil |
72 |
Dielectric dissipation factor at 90 ºC | 0.00025 |
Specific resistance (resistivity) a) A:90 ºC b) A:27 ºC |
750x1012 ohm-cm 11300x1012 ohm-cm |
Oxidation stability a) Neutralization value after oxidation, mg KOH/g b) Total sludge after oxidation,% by wt. |
0.4 0.1 |
AGEING CHARACTERISTICS AFTER AGEING | |
Open breaker method with copper characteristics | |
Specific resistance (resistivity) a) A:27 ºC b) A:90 ºC c) dielectric dissipation factor at 90 ºC d) total acidity e) total sludge |
350x10M12 ohm-cm 19x1012 ohm-cm 0.0025/2.08 DC NIL NIL |
Presence of oxidation inhibitor,% by wt | Absent |
Water content, mg/kg(ppm) | 50 |
SK value (%) | 1 |
APPROVALS:
HP TRANSFORMER OIL is certified Central Power Research Institute (CPRI), Bangalore and Electrical Research and Development Association (ERDA), Vadodara